| EXCEPTIONS: | 1. Means of egress complying with Section 1028. |
| 2. For other than H and I-2 occupancies, the total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by 0.2 inches (5.1 mm) per occupant for stairways and by 0.15 inches (3.8 mm) per occupant for other egress components in buildings that are provided with sprinkler protection in accordance with 903.3.1.1 or 903.3.1.2 and an emergency voice/alarm communication system in accordance with 907.5.2.2. |
| EXCEPTIONS: | 1. Accessible means of egress are not required in alterations to existing buildings. |
| 2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3, 1007.4 or 1007.5. | |
| 3. In assembly areas with sloped or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1028.8. | |
| 4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces. |
| EXCEPTIONS: | 1. Two-way communication systems are not required at the elevator landing where two-way communication is provided within the areas of refuge in accordance with Section 1007.6.3. |
| 2. Two-way communication systems are not required on floors provided with exit ramps conforming to provisions of Section 1010. |
| EXCEPTION: | Items 1, 2, 3, and 5 shall not apply to doors to areas where persons which because of clinical needs require restraint or containment as part of the function of a Group I-2 mental hospital provided that all clinical staff shall have the keys, codes or other means necessary to operate the locking devices. |
| EXCEPTIONS: | 1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through1108.2.4 and 1108.2.6, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1028.11. |
| 2. Curb ramps shall comply with ICC A117.1. | |
| 3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.3 through 1010.9 when they are not an accessible route serving accessible parking spaces or other required accessible elements. | |
| 4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area may include a vehicle ramp that does not comply with Sections 1010.4 through 1010.8. |
| EXCEPTION: | Rooms with exit doors opening directly to the outside at ground level. |
| EXCEPTIONS: | 1. Use of a corridor as a source of makeup air for exhaust systems in rooms that open directly onto such corridors, including toilet rooms, bathrooms, dressing rooms, smoking lounges and janitor closets, shall be permitted, provided that each such corridor is directly supplied with outdoor air at a rate greater than the rate of makeup air taken from the corridor. |
| 2. Where located within a dwelling unit, the use of corridors for conveying return air shall not be prohibited. | |
| 3. Where located within tenant spaces of one thousand square feet (93 m2) or less in area, utilization of corridors for conveying return air is permitted. | |
| 4. Incidental air movement from pressurized rooms within health care facilities, provided that a corridor is not the primary source of supply or return to the room. | |
| 5. Where such air is part of an engineered smoke control system. | |
| 6. Air supplied to corridors serving residential occupancies shall not be considered as providing ventilation air to the dwelling units subject to the following: | |
| 6.1 The air supplied to the corridor is one hundred percent outside air; and | |
| 6.2 The units served by the corridor have conforming ventilation air independent of the air supplied to the corridor; and | |
| 6.3 For other than high-rise buildings, the supply fan will automatically shut off upon activation of corridor smoke detectors which shall be spaced at no more than thirty feet (9,144 mm) on center along the corridor; or | |
| 6.4 For high-rise buildings, corridor smoke detector activation will close required smoke/fire dampers at the supply inlet to the corridor at the floor receiving the alarm. |
| EXCEPTIONS: | 1. Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. |
| 2. In Group R-2 boarding homes and residential treatment facilities licensed by Washington state, seating areas shall be allowed to be open to the corridor provided: | |
| 2.1 The seating area is constructed as required for the corridor; | |
| 2.2 The floor is separated into at least two compartments complying with Section 407.4; | |
| 2.3 Each individual seating area does not exceed 150 square feet, excluding the corridor width; | |
| 2.4 The combined total space of seating areas per compartment does not exceed 300 square feet, excluding the corridor width; | |
| 2.5 Combustible furnishings located within the seating area shall be in accordance with the International Fire Code Section 805; and | |
| 2.6 Emergency means of egress lighting is provided as required by Section 1006 to illuminate the area. |