503.1 Where required. Fire apparatus access roads shall be
provided and maintained in accordance with locally adopted
street, road, and access standards.
503.2 Specifications. This section is not adopted.
503.3 Marking. This section is not adopted.
503.4 Obstruction of fire apparatus access roads. This
section is not adopted.
SECTION 507 FIRE PROTECTION WATER SUPPLIES
507.3 Fire flow. Fire flow requirements for buildings or
portions of buildings and facilities shall be determined by an
approved method.
EXCEPTION:
Fire flow is not required for structures under 500 square feet with a B, U or R-1 occupancy where structures are at least
30 feet from any other structure and are used only for recreation.
SECTION 508 FIRE COMMAND CENTER
508.1.2 Separation. The fire command center shall be
separated from the remainder of the building by not less than
a 2-hour fire barrier constructed in accordance with Section
707 of the International Building Code or horizontal assembly
constructed in accordance with Section 712 of the
International Building Code, or both.