Section 504 -- Clothes dryer exhaust.
504.6.4.1 Specified length. The maximum length of the exhaust
duct shall be 35 feet (10668 mm) from the connection to the
transition duct from the dryer to the outlet terminal. Where
fittings are used, the maximum length of the exhaust duct
shall be reduced in accordance with Table 504.6.4.1.
The maximum length of the duct may be increased in an
engineered exhaust system when a listed and labeled exhaust
booster fan is installed in accordance with the manufacturer's
installation instructions.