| EXCEPTION: |
The total area of ventilation openings shall be permitted to be reduced to 1/1,500 of the under-floor area where the
ground surface is covered with an approved Class I vapor retarder material and the required openings are placed to
provide cross ventilation of the space. The installation of operable louvers shall not be prohibited. If the installed
ventilation is less than 1/300, or if operable louvers are installed, a radon vent shall be installed to originate from a
point between the ground cover and soil. The radon vent shall be installed in accordance with the requirements of
Appendix F (Radon) of this code. |