| EXCEPTIONS: |
1. The minimum required net free ventilating shall be 1/300 of the area of the space ventilated, provided a vapor
retarder having a transmission rate not exceeding one perm in accordance with ASTM E 96 is installed on the warm
side of the attic insulation and provided 50 percent of the required ventilating area provided by ventilators located in
the upper portion of the space to be ventilated is at least 3 feet (914 mm) above eave or cornice vents, with the
balance of the required ventilation provided by eave or cornice vents. |
|
2. Unvented attic assemblies (spaces between the ceiling joists of the top story and the roof rafters) shall be permitted
if all the following conditions are met: |
|
2.1 The unvented attic space is completely contained within the building thermal envelope. |
|
2.2 No interior vapor retarders are installed on the ceiling side (attic floor) of the unvented attic assembly. |
|
2.3 Where wood shingles or shakes are used, a minimum 1/4 inch (6 mm) vented air space separates the shingles or
shakes and the roofing underlayment above the structural sheathing. |
|
2.4 Any air-impermeable insulation shall be a vapor retarder, or shall have a vapor retarder coating or covering in
direct contact with the underside of the insulation. |
|
2.5 Either items a, b, or c below shall be met, depending on the air permeability of the insulation directly under the
structural roof sheathing. |
|
a. Air-impermeable insulation only. Insulation shall be applied in direct contact to the underside of the structural roof
sheathing. |
|
b. Air-permeable insulation only. In addition to the air-permeable insulation installed directly below the structural
sheathing, rigid board or sheet insulation shall be installed directly above the structural roof sheathing as specified per
WA Climate Zone for condensation control. |
|
i. Climate Zone #1 - R-10 minimum rigid board or air-impermeable insulation R-value. |
|
ii. Climate Zone #2 - R-25 minimum rigid board or air-impermeable insulation R-value. |
|
c. Air-impermeable and air-permeable insulation. The air-impermeable insulation shall be applied in direct contact to
the underside of the structural roof sheathing as specified per WA Climate Zone for condensation control. The
air-permeable insulation shall be installed directly under the air-impermeable insulation. |
|
i. Climate Zone #1 - R-10 minimum rigid board or air-impermeable insulation R-value. |
|
ii. Climate Zone #2 - R-25 minimum rigid board or air-impermeable insulation R-value. |
| EXCEPTION: |
A fan for subslab depressurization system includes the following: |
|
1. Soil-gas retarder membrane as specified in Section 1203.6.3.2.4; |
|
2. Sealing of penetrations and joints as specified in Section 1203.6.3.2.5; |
|
3. A 3-inch continuous sealed radon pipe shall run from a point within the aggregate under each concrete slab to a
point outside the building; |
|
4. Joints and connections shall be gas tight, and may be of either PVC schedule 40 or ABS schedule of equivalent in
wall thickness; |
|
5. A label of "radon vent" shall be placed on the pipe so as to remain visible to an occupant; |
|
6. Fan circuit and wiring as specified in Section 1203.6.3.2.7 and a fan. |