WAC 51-50-1014   Exit access.  


1014.2.2 Group I-2.


General. Habitable spaces and suites in Group I-2 occupancies are permitted to comply with this Section 1014.2.2.


1014.2.2.1 Exit access doors. Habitable spaces and suites in Group I-2 occupancies shall have an exit access door leading directly to a corridor.


EXCEPTION: Rooms with exit doors opening directly to the outside at ground level.

1014.2.2.2 Exit access through suites. Exit access from areas not classified as a Group I-2 Occupancy suite shall not pass through a suite. In a suite required to have more than one exit, one exit access may pass through an adjacent suite if all other requirements of Section 1014.2 are satisfied.


1014.2.2.3 Separation. Suites in Group I-2 Occupancies shall be separated from other portions of the building by a smoke partition complying with Section 711. Partitions within suites are not required to be smoke-resistant or fire-resistance-rated unless required by another section of this Code.


1014.2.2.4 Suites containing patient sleeping areas. Patient sleeping areas in Group I-2 Occupancies shall be permitted to be divided into suites with one intervening room if one of the following conditions is met:


     1. The intervening room within the suite is not used as an exit access for more than eight patient beds.


     2. The arrangement of the suite allows for direct and constant visual supervision by nursing personnel.


1014.2.2.4.1 Area. Suites of sleeping rooms shall not exceed 5,000 square feet (465 m2).


1014.2.2.4.2 Exit access. Any patient sleeping room, or any suite that includes patient sleeping rooms, of more than 1,000 square feet (93 m2) shall have at least two exit access doors located in accordance with Section 1015.2.


1014.2.2.4.3 Travel distance. The travel distance between any point in a suite of sleeping rooms and an exit access door of that suite shall not exceed 100 feet (30,480 mm). The travel distance between any point in a Group I-2 Occupancy patient sleeping room and an exit access door in that room shall not exceed 50 feet (15,240 mm).


1014.2.2.5 Suites not containing patient sleeping areas. Areas other than patient sleeping areas in Group I-2 Occupancies shall be permitted to be divided into suites that comply with Sections 1014.2.2.5.1 through 1014.2.2.5.4.


1014.2.2.5.1 Area. Suites of rooms, other than patient sleeping rooms, shall not exceed 10,000 square feet (929 m2).


1014.2.2.5.2 Exit access. Any rooms or suite of rooms, other than patient sleeping rooms, of more than 2,500 square feet (232 m2) shall have at least two exit access doors located in accordance with Section 1015.2.


1014.2.2.5.3 One intervening room. For rooms other than patient sleeping rooms, suites of rooms are permitted to have one intervening room if the travel distance within the suite to the exit access door is not greater than 100 feet (30,480 mm).


1014.2.2.5.4 Two intervening rooms. For rooms other than patient sleeping rooms located within a suite, exit access travel from within the suite shall be permitted through two intervening rooms where the travel distance to the exit access door is not greater than 50 feet (15,240 mm).



[Statutory Authority: RCW 19.27.031 and 19.27.074. 10-03-097, § 51-50-1014, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-1014, filed 12/19/06, effective 7/1/07.]