WAC 16-229-410
Backflow prevention. (1) When piping within
a permanent mixing/loading site is directly connected to a water
source such as a well or public water system, an approved air gap
or an approved reduced pressure principle backflow prevention
assembly (RPBA) shall be installed to protect the water source.
Approved air gaps and approved RPBA's shall be installed,
operated, inspected and/or tested and maintained per WAC 246-290-490.
(2) Approved RPBA's shall be inspected and tested once per
year by a Washington state department of health certified
backflow assembly tester, and approved air gaps shall be
inspected by a Washington state department of health certified
backflow assembly tester or cross-connection control
specialist[:]
(a) At the time of installation, alteration or relocation,
and at least on an annual schedule thereafter.
[Statutory Authority: Chapters 15.58 and 17.21 RCW. 00-23-074,
§ 16-229-410, filed 11/17/00, effective 12/18/00. Statutory
Authority: RCW 15.54.800 and 15.58.040. 93-22-093 (Order 5018),
§ 16-229-410, filed 11/2/93, effective 3/1/94.]