WAC 16-202-1021
What alternative methods can be used as a
system interlock? Alternative technology used as a system
interlock must fulfill the provisions of this chapter.
(1) A person may not serve as a human interlock.
(2) Solenoid and check valve.
(a) The chemical injection line must contain either a
normally closed solenoid-operated valve connected to the system
interlock or a normally closed hydraulically operated valve that
opens only when the main water line is adequately pressurized. A
normally closed, solenoid-operated valve must be placed on the
intake side of the injection pump, immediately adjacent to the
application tank.
(b) The chemical injection line between the application tank
and the metering device must contain an automatic, quick-closing
check valve to prevent the flow of liquid back toward the
application tank. The check valve must be placed immediately
adjacent to the venturi chemical inlet.
[Statutory Authority: Chapters 15.54, 15.58, 17.21, and 34.05 RCW. 01-23-018, § 16-202-1021, filed 11/9/01, effective
11/9/01.]