WAC 296-305-04511
Elevated platforms. (1) Elevated
platform system design requirements:
(a) The platform shall have a minimum floor area of fourteen
square feet.
(b) The platform shall be provided with a guard railing. The guard railing shall be 42 to 45 inches high on all sides.
(c) The railing shall be constructed so that there is no
opening below it greater than 19 inches.
(d) There shall be two gates below the top railing, each of
which shall be provided with suitable safety latches.
(e) A kick plate not less than four inches high shall be
provided around the floor of the platform.
(f) Drain openings shall be provided to prevent water
accumulation on the platform.
(g) A heat-protective shield shall be provided on the
platform for the protection of the operator.
(h) Hydraulic or pneumatic systems shall have a minimum
bursting strength of at least four times the operating pressure
for which the system is designed.
(i) The basic structural elements of the hydraulic or
articulating boom shall have a safety factor of three.
(j) Each hydraulic or pneumatic system for the boom shall be
equipped with a pilot operated check valve or other appropriate
device to prevent free fall in the event of hydraulic failure.
(2) Requirements related to the controlling of elevated
platforms:
(a) A control or device shall be provided at both the lower
control station and the platform control station to allow either
operator to completely deactivate the platform controls.
(b) During the deactivation of the platform controls, the
lower controls shall remain operable.
(c) A plate shall be located at the platform control unit or
units listing the following information:
(i) Model and serial number of the manufacturer;
(ii) Rated capacity of the platform;
(iii) Operating pressure of the hydraulic or pneumatic
systems or both;
(iv) Caution or restriction of operation or both; and
(v) Control instructions.
(vi) This plate shall be clearly visible to the operator at
the lower control position.
(d) There shall be an operator at the lower controls at all
times while the fire fighter is in the bucket.
(e) The operator at the lower controls shall make certain
the fire fighter on the platform is secured by his life belt, or
equivalent, before raising the platform.
(3) Testing of elevated platforms and related apparatus
shall be conducted annually.
(a) Testing of elevated platforms and related apparatus
shall be in accordance with NFPA, Standard for Testing Fire
Department Aerial Ladders 1914, 1991 edition.
(b) It is recommended that the boom section as well as the
support section of the apparatus which supports the turntable
should be nondestructively tested by a certified testing agency
every five years.
(c) After any accident that causes structural damage,
testing shall be performed and all defects detected shall be
corrected before the apparatus is returned to service.
(d) Elevated platform testing shall follow recommendations
of the current National Fire Code.
(e) Fire apparatus elevated platforms shall be positioned
for the greatest stability feasible at the fire scene.
(4) A two-way voice communication system shall be installed
between the platform and the lower control station.
(5) Automotive apparatus used in conjunction with elevated
platforms shall be used in accordance with the following:
(a) Hand or air brakes shall be set before the platform is
operated.
(b) Jacks or outriggers shall be used if the platform is to
be elevated.
(c) Wheel blocks shall also be used when the platform is in
operation unless the type of apparatus is one that has wheels
that lift off the ground when the jacks or outriggers are
engaged.
(d) Ground plates shall be used under the outriggers or
jacks.
(e) Sand shall be put under jacks and outriggers when
operating on ice or snow.
(f) When working on or near energized electrical lines, the
fire department shall develop operational procedures for
observing the following minimum working clearances:
(i) For lines rated 50 kv or below, the minimum clearance
shall be ten feet.
(ii) For lines rated over 50 kv, the minimum clearance shall
be ten feet plus 0.4 inch for each 1 kv.
(iii) For low voltage lines (operating at 750 volts or
less), the work shall be performed in a manner to prevent the
fire fighters contacting the energized conductor.
(6) Appliances mounted on elevated platforms. Platform
mounted monitors shall be operated in accordance with the
manufacturer's instructions.
Additional References: WAC 296-24-880.
[Statutory Authority: RCW 49.17.010, [49.17].040, and[49.17].050
. 01-11-038, § 296-305-04511, filed 5/9/01, effective
9/1/01. Statutory Authority: RCW 49.17.010, [49.17].050 and[49.17].060
. 96-11-067, § 296-305-04511, filed 5/10/96,
effective 1/1/97.]