WAC 246-361-070
Electricity and lighting. (1) General
electricity requirements.
(a) The operator must supply electricity to all dwelling
units, kitchen facilities, bathroom facilities, common areas, and
laundry facilities.
(b) All electrical wiring, fixtures and electrical equipment
must comply with department of labor and industries regulations,
chapter 19.28 RCW and local ordinances, and maintained in a safe
condition.
(2) Electricity requirements in tents.
(a) Each individual tent must have at least one separate
floor-type or wall-type convenience outlet. If the operator
provides a refrigerator in the tent, a dedicated outlet must be
provided for it.
(b) All electrical wiring and equipment installed in tents
must meet the requirements of WAC 296-46-100.
(c) All electrical appliances to be connected to the
electrical supply must meet the requirements for the load
calculations as required by chapter 19.28 RCW.
(d) Electrical wiring exiting the tent to connect to the GFI
outside outlet must be placed in approved flexible conduit not to
exceed six feet in length.
(e) All wiring located inside the tent must be placed in
conduit for protection and connected to a surface to secure the
wiring to prevent movement. Wiring must be located to prevent
tripping or safety hazards.
(f) Receptacles and lighting fixtures must be UL Listed and
approved by the department for use in the tent.
(3) General lighting requirements.
(a) The operator must provide adequate lighting sufficient
to carry on normal daily activities in all common use areas.
(b) Laundry and toilet rooms and rooms where people
congregate must have at least one ceiling-type or wall-type
fixture. Where portable toilets are used, lighting requirements
can be met by area illumination.
(c) The operator must provide adequate lighting for safe
passage for camp occupants to handwashing sinks and toilets.
(d) The operator must provide adequate lighting for shower
rooms during hours of operation.
Note: Lighting requirements may be met by natural or
artificial means.
(4) Lighting requirements in tents.
(a) Tents must have adequate lighting sufficient to carry on
all normal daily activities. For example: Three 100-watt bulbs
located at the top ridge of the frame and are UL Listed or
equivalent.
(b) Each tent must have at least one ceiling-type light
fixture.
(c) Food preparation areas, if located in the tent, must
have at least one lighting fixture located to provide task
lighting over the food preparation area.
(d) Alternate lighting appliances must provide adequate
lighting. In addition, if using two or more propane, butane, or
white gas lighting appliances, a carbon monoxide monitor must be
provided and located not more than thirty inches from the floor.
[Statutory Authority: RCW 70.114A.065 and 70.114A.110. 00-06-082, § 246-361-070, filed 3/1/00, effective 3/1/00.]