WAC 51-50-3004
Section 3004 -- Hoistway venting.
3004.3 Area of vents. Except as provided for in Section3004.3.1
, the area of the vents shall not be less than 3 1/2
percent of the area of the hoistway nor less than 3 square
feet (0.28 m2) for each elevator car, and not less than 3 1/2
percent nor less than 0.5 square feet (0.047 m3) for each
dumbwaiter car in the hoistway, whichever is greater. The
total required vent area shall be equipped with dampers that
remain powered closed until activated open by the fire alarm
system panel. The dampers shall open upon loss of power.
[Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-3004, filed
12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-3004, filed
12/17/03, effective 7/1/04.]