| EXCEPTION: | In occupancies serving 15 or fewer persons, one toilet facility designed for use by no more than one person at a time shall be permitted for use by both sexes. |
| EXCEPTIONS: | 1. Sporting facilities with concessions serving drinks shall have one drinking fountain for each 1000 occupants. |
| 2. A drinking fountain need not be provided in a drinking or dining establishment. |
| TYPE OF BUILDING OR OCCUPANCY8 | WATER CLOSETS (fixtures per person) |
LAVATORIES5 (fixtures per person) |
BATHTUB OR SHOWER (fixtures per person) |
||
| MALE3 | FEMALE | MALE | FEMALE | ||
| For the occupancies listed below, use 30 square feet (2.79 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group A Assembly places -- |
|||||
| Conference rooms, dining rooms, drinking establishments, exhibit rooms, gymnasiums, lounges, stages and similar uses including restaurants classified as Group B Occupancies | 1:1-25 | 1:1-25 | One per 2 water closets | ||
| 2:26-75 | 2:26-75 | ||||
| 3:76-125 | 3:76-125 | ||||
| 4:126-200 | 4:126-200 | ||||
| 5:201-300 | 5:201-300 | ||||
| 6:301-400 | 6:301-400 | ||||
| Over 400, add one fixture for each additional 200 males or 150 females | |||||
| For the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 15 square feet (1.39 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Assembly places -- 9 Theaters, auditoriums, convention halls, dance floors, lodge rooms, casinos, and such places which have limited time for fixture use (intermissions) |
1:1-100 | One per 25 | 1:1-200 | 1:1-200 | |
| 2:101-200 | Up to 400 | 2:201-400 | 2:201-400 | ||
| 3:201-400 | 3:401-750 | 3:401-750 | |||
| Over 400, add one fixture for each additional 250 males or 50 females | Over 750, add one fixture for each additional 500 persons | ||||
| Assembly places -- Stadiums, arena and other sporting facilities where fixture use is not limited to intermissions |
1:1-100 | One per 50 | 1:1-200 | 1:1-200 | |
| 2:101-200 | Up to 400 | 2:201-400 | 2:201-400 | ||
| 3:201-400 | 3:401-750 | 3:401-750 | |||
| Over 400, add one fixture for each additional 300 males or 100 females | Over 750, add one fixture for each additional 500 persons | ||||
| For the assembly occupancies listed below, use the number of fixed seating or, where no fixed seating is provided, use 30 square feet (2.79 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Worship places | |||||
| Principal assembly area | One per 150 | One per 75 | One per 2 water closets | ||
| Educational & activity unit | One per 125 | One per 75 | One per 2 water closets | ||
| For the occupancies listed below, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group B and other clerical or administrative employee accessory use |
1:1-15 | 1:1-15 | One per 2 water closets | ||
| 2:16-35 | 2:16-35 | ||||
| 3:36-55 | 3:36-55 | ||||
| Over 55, add one for each additional 50 persons | |||||
| For the occupancies listed below, use 100 square feet ( 9.3 m2) per student for the minimum number of plumbing fixtures. | |||||
| Group E | 1:1-15 | 1:1-15 | One per 2 water closets | ||
| Schools - for staff use | 2:16-35 | 2:16-35 | |||
| All schools | 3:36-55 | 3:36-55 | |||
| (One staff per 20 students) | Over 55, add one fixture for each additional 40 persons | ||||
| Schools - for student use | 1:1-20 | 1:1-20 | 1:1-20 | 1:1-20 | |
| Day care | 2:21-50 | 2:21-50 | 2:21-50 | 2:21-50 | |
| Over 50, add one fixture for each additional 50 persons | Over 50, add one fixture for each additional 50 persons | ||||
| Elementary | One per 30 | One per 25 | One per 2 water closets | ||
| Secondary | One per 40 | One per 30 | One per 2 water closets | ||
| For the occupancies listed below, use 50 square feet (4.65 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Education facilities other than Group E | |||||
| Others (colleges, universities, adult centers, etc.) | One per 40 | One per 25 | One per 2 water closets | ||
| For the occupancies listed below, use 2,000 square feet (185.8 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group F and Group H | 1:1-10 | 1:1-10 | One per 2 water closets | ||
| Workshop, foundries and
similar establishments,
and hazardous
occupancies |
2:11-25 | 2:11-25 | One shower for each 15 persons exposed to excessive heat or to skin contamination with irritating materials | ||
| 3:26-50 | 3:26-50 | ||||
| 4:51-75 | 4:51-75 | ||||
| 5:76-100 | 5:76-100 | ||||
| Over 100, add one fixture for each additional 30 persons | |||||
| For the occupancies listed below, use the designated application and 200 square feet (18.58 m2) per occupant of the general use area for the minimum number of plumbing fixtures. | |||||
| Group I7 | |||||
| Hospital waiting rooms | One per room (usable by either sex) | One per room | |||
| Hospital general use areas |
1:1-15 | 1:1-15 | One per 2 water closets | ||
| 2:16-35 | 3:16-35 | ||||
| 3:36-55 | 3:36-55 | ||||
| Over 55, add one fixture for each additional 40 persons | |||||
| Hospital patient rooms: | |||||
| Single Bed | One adjacent to and directly accessible from | One per toilet room | One per toilet room | ||
| Isolation | One adjacent to and directly accessible from | One per toilet room | One per toilet room | ||
| Multibed | One per 4 patients | One per 4 patients | One per 8 patients | ||
| Long-term | One per 4 patients | One per 4 patients | One per 15 patients | ||
| Jails and reformatories | |||||
| Cell | One per cell | One per cell | |||
| Exercise room | One per exercise room | One per exercise room | |||
| Other institutions (on each occupied floor) | One per 25 | One per 25 | One per 2 water closets | One per 8 | |
| For the occupancies listed below, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group M | |||||
| Retail or wholesale stores | 1:1-50 | 1:1-50 | One per 2 water closets | ||
| 2:51-100 | 2:51-100 | ||||
| 3:101-400 | 3:101-200 | ||||
| 4:201-300 | |||||
| 5:301-400 | |||||
| Over 400, add one fixture for each additional 300 males or 150 females | |||||
| For Group R Occupancies containing dwelling units or guest rooms, use the table below. For dormitories, use 200 square feet (18.58 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group R | |||||
| Dwelling units | One per dwelling unit | One per dwelling unit | One per dwelling unit | ||
| Hotel, motel, and boarding house guest rooms | One per guest room | One per guest room | One per guest room | ||
| Boarding homes licensed by the department of social and health services | One per 8 | One per 8 | One per 8 | One per 8 | One per 12 |
| Dormitories | One per 10 | One per 8 | One per 12 | One per 12 | One per 8 |
| Over 10, add one fixture for each additional 25 males and over 8, add one for each additional 20 females | Over 12, add one fixture for each additional 20 males and one for each additional 15 females | For females, add one additional unit per each additional 30. Over 150 persons, add one additional unit per each additional 20 persons | |||
| For the occupancies listed below, use 5,000 square feet (464.5 m2) per occupant for the minimum number of plumbing fixtures. | |||||
| Group S | 1:1-10 | 1:1-10 | One per 40 occupants of each sex | One shower for each 15 persons exposed to excessive heat or to skin contamination with poisonous, infectious or irritating materials | |
| Warehouses | 2:11-25 | 2:11-25 | |||
| 3:26-50 | 3:26-50 | ||||
| 4:51-75 | 4:51-75 | ||||
| 5:76-100 | 5:76-100 | ||||
| Over 100, add one for each 30 persons | |||||
| 1The figures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction thereof. | |
| 2For occupancies not shown, see Section 2902.1.1. | |
| 3Where urinals are provided, one water closet less than the number specified may be provided for each urinal installed, except the number of water closets in such cases shall not be reduced to less than one quarter (25%) of the minimum specified. For men's facilities serving 26 or more persons, not less than one urinal shall be provided. | |
| 4For drinking fountains, see Section 2903.4. | |
| 5Twenty-four inches (610 mm) of wash sink or 18 inches (457 mm) of a circular basin, when provided with water outlets for such space, shall be considered equivalent to one lavatory. | |
| 6For when a facility may be usable by either sex, see Section 2902.3.1. | |
| 7See WAC 246-320 for definitions, other fixtures and equipment for hospitals. | |
| 8When a space is accessory to or included as a part of a different occupancy group per Chapter 3, the area per occupant for the minimum plumbing fixture number is to be determined by its own specific use or purpose, not by that of the building's occupancy group. | |
| 9In multiplex movie theaters, where shows are scheduled at different times, the number of occupants for toilet fixture use may be based upon one-half (50%) of the total in all the auditoriums, but no less than the number in the largest auditorium. |