WAC 51-50-1101   Section 1101 -- General.  


1101.2 Design. Buildings and facilities shall be designed and constructed to be accessible in accordance with this code and ICC A117.1, except those portions of ICC A117.1 amended by this section.


1101.2.1 (ICC A117.1 Section 403) Landings for walking surfaces. The maximum rise for any run is 30 inches (762 mm). Landings shall be provided at the top and bottom of any run. Landings shall be level and have a minimum dimension measured in the direction of travel of not less than 60 inches (1525 mm).


1101.2.2 (ICC A117.1 Section 403.5) Clear width of accessible route. Clear width of an accessible route shall comply with ICC A117.1 Table 403.5. For exterior routes of travel, the minimum clear width shall be 44 inches (1118 mm).


1101.2.3 (ICC A117.1 Section 404.2.8) Door-opening force. Fire doors shall have the minimum opening force allowable by the appropriate administrative authority. The force for pushing or pulling open doors other than fire doors shall be as follows:

     1. Interior hinged door: 5.0 pounds (22.2 N) maximum

     2. Interior sliding or folding doors: 5.0 pounds (22.2 N) maximum

     3. Exterior hinged, sliding or folding door: 10 pounds (44.4 N) maximum.


EXCEPTION: Interior or exterior automatic doors complying with Section 404.3 of ICC ANSI A117.1.

     These forces do not apply to the force required to retract latch bolts or disengage other devices that hold the door in a closed position.


1101.2.4 (ICC A117.1 Section 407.4.6.2.2) Arrangement of elevator car buttons. This section is not adopted.


1101.2.5 (ICC A117.1 603.4) Coat hooks and shelves. Coat hooks shall be located within one of the reach ranges specified in Section 308. Shelves shall be installed so the top of the shelf is 40 inches (1015 mm) minimum and 42 inches maximum above the floor.


1101.2.6 (ICC A117.1 604.11) Coat hooks and shelves. Coat hooks provided within toilet compartments shall be located within one of the reach ranges specified in Section 308. Shelves shall be installed so the top of the shelf is 40 inches (1015 mm) minimum and 42 inches maximum above the floor.


1101.2.7 (ICC ANSI A117.1 606.7) Operable parts. Operable parts on drying equipment, towel or cleansing product dispensers, and disposal fixtures shall comply with Table 606.7, except the maximum reach height shall be 40 inches (1015 mm) for reach depths less than 6 inches.


1101.2.8 (ICC A117.1 Section 604.6) Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309, except the maximum height above the floor shall be 44 inches. Flush controls shall be located on the open side of the water closet.


EXCEPTION: In ambulatory accessible compartments complying with Section 604.9, flush controls shall be permitted to be located on either side of the water closet.



1101.2.9 (ICC A117.1 Section 703.6.3.1) International Symbol of Accessibility. Where the International Symbol of Accessibility is required, it shall be proportioned complying with ICC A117.1 Figure 703.6.3.1. All interior and exterior signs depicting the International Symbol of Accessibility shall be white on a blue background.


1101.2.10 (ICC A117.1 Section 404.3.5) Control switches. Manually operated control switches shall comply with Section 309, except they shall be placed 32 inches minimum (815 mm) and 40 inches maximum (1015 mm) above the floor. The clear floor space adjacent to the control switch shall be located beyond the arc of the door swing and centered on the control switch.



[Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-1101, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.020, 19.27.031, 19.27.074, and chapters 19.27 and 34.05 RCW. 05-24-070, § 51-50-1101, filed 12/5/05, effective 7/1/06; 05-01-014, § 51-50-1101, filed 12/2/04, effective 7/1/05. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-1101, filed 12/17/03, effective 7/1/04.]