TABLE 1019.2 (IFC 1019.2)
BUILDINGS WITH ONE EXIT
| OCCUPANCY |
MAXIMUM
HEIGHT OF
BUILDING
ABOVE
GRADE
PLANE |
MAXIMUM
OCCUPANTS
(OR DWELLING
UNITS) PER
FLOOR AND
TRAVEL
DISTANCE |
| A, Bd, Ee, F, M, U |
1 Story |
49 occupants and
75 feet travel
distance |
| H-2, H-3 |
1 Story |
3 occupants and
25 feet travel
distance |
| H-4, H-5, I, R |
1 Story |
10 occupants and
75 feet travel
distance |
| Sa |
1 Story |
29 occupants and
100 feet travel
distance |
| Bb, F, M, Sa |
2 Stories |
30 occupants and
75 feet travel
distance |
| R-2 |
2 Storiesc |
4 dwelling units
and 50 feet travel
distance |
|
For SI: 1 foot = 304.8 mm. |
|
a. For the required number of exits for open parking structures, see Section 1019.1.1. |
|
b. For the required number of exits for air traffic control towers, see Section 412.1. |
|
c. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescue openings in accordance with Section
1026 shall have a maximum height of three stories above grade plane. |
|
d. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 with an
occupancy in Group B shall have a maximum travel distance of 100 feet. |
|
e. Day care maximum occupant load is 10. |