WAC 51-50-0903   Section 903 -- Automatic sprinkler systems.  


903.2.1.6 Nightclub. An automatic sprinkler system shall be provided throughout Group A-2 nightclubs as defined in this code. An existing nightclub constructed prior to July 1, 2006, shall be provided with automatic sprinklers not later than December 1, 2009.


903.2.2 Group E. An automatic sprinkler system shall be provided for Group E Occupancies.


EXCEPTIONS: 1. Portable school classrooms, provided aggregate area of any cluster or portion of a cluster of portable school classrooms does not exceed 5,000 square feet (1465 m2); and clusters of portable school classrooms shall be separated as required in chapter 5 of the building code.
2. Group E occupancies with an occupant load of 50 or less.

903.2.7 Group R. An automatic fire sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.


EXCEPTION: Group R-1 if all of the following conditions apply:
1. The Group R fire area is no more than 500 square feet and is used for recreational use only.
2. The Group R fire area is only one story.
3. The Group R fire area does not include a basement.
4. The Group R fire area is no closer than 30 feet from another structure.
5. Cooking is not allowed within the Group R fire area.
6. The Group R fire area has an occupant load of no more than 8.
7. A hand held (portable) fire extinguisher is in every Group R fire area.




[Statutory Authority: RCW 19.27.190, 19.27.020, and chapters 19.27 and 34.05 RCW. 08-01-110, § 51-50-0903, filed 12/18/07, effective 4/1/08. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-0903, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.020, 19.27.031, 19.27.074, and chapters 19.27 and 34.05 RCW. 05-24-070, § 51-50-0903, filed 12/5/05, effective 7/1/06. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-0903, filed 12/17/03, effective 7/1/04.]