WAC 51-50-0707
Section 707 -- Shaft enclosures.
707.14.2 Enclosed elevator lobby pressurization alternative.
Where elevator hoistway pressurization is provided in lieu of
required enclosed elevator lobbies, the pressurization system
shall comply with this section.
707.14.2.1 Pressurization requirements. Elevator hoistways
shall be pressurized to maintain a minimum positive pressure
of 0.10 inches of water column with respect to adjacent
occupied space on all floors and a maximum pressure so as to
not prevent the automatic operation of the elevator doors, as
well as accounting for the stack and wind effect expected on
the mean low temperature January day. This pressure shall be
measured at the midpoint of each hoistway door, with all
hoistway doors open at the designated primary recall level and
all other hoistway doors closed. The supply air intake shall
be from an outside, uncontaminated source located a minimum
distance of 20 feet from any air exhaust system or outlet.
707.14.2.2 Ducts for system. Any duct system that is part of
the pressurization system shall be protected with the same
fire-resistance rating as required for the elevator shaft
enclosure.
707.14.2.3 Fan system. The fan system provided for the
pressurization system shall be as required by this section.
707.14.2.3.1 Fire resistance. When located within the
building, the fan system that provides the pressurization
shall be protected with the same fire-resistance rating
required for the elevator shaft enclosure.
707.14.2.3.2 Smoke detection. The fan system shall be
equipped with a smoke detector that will automatically shut
down the fan system when smoke is detected within the system.
707.14.2.3.3 Separate systems. A separate fan system shall be
used for each bank of elevators.
707.14.2.3.4 Fan capacity. The supply fan shall either be
adjustable with a capacity of at least 1000-cfm (.4719 m3/s)
per door, or that specified by a registered design
professional to meet the requirements of a designed
pressurization system.
707.14.2.4 Standby power. The pressurization system shall be
provided with standby power from the same source as other
required emergency systems for the building.
707.14.2.5 Activation of pressurization system. The elevator
pressurization system shall be activated upon activation of
the building fire alarm system or upon activation of the
elevator lobby smoke detectors.
707.14.2.6 Elevator doors. Each elevator door shall operate
properly when hoistway pressurization is in effect.
707.14.2.7 Hoistway venting. Hoistway venting required by
Section 3004 need not be provided for pressurized elevator
shafts.
707.14.2.8 Machine rooms. Elevator machine rooms shall be
pressurized in accordance with this section unless separated
from the hoistway shaft by construction in accordance with
Section 707.
707.14.2.9 Special inspection. Special inspection for
performance shall be required in accordance with Section909.18.8
. System acceptance shall be in accordance with
Section 909.19.
[Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. 07-01-091, § 51-50-0707, filed
12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27.031 and 19.27.074. 04-01-108, § 51-50-0707, filed
12/17/03, effective 7/1/04.]