WAC 51-19-620   Fire safety.  (1) When a change of occupancy is made to a higher hazard group as shown in Table No. VI-1, all elements of the exit system shall comply with the requirements of the Building Code.


EXCEPTIONS: (a) Existing exit corridors and stairways meeting the requirements of Part IV of this chapter may be used.
(b) Exit system elements may meet alternative compliance requirements as approved by the building official.

     (2) Existing exit systems complying with Part IV shall be accepted if the occupancy change is to an equal or lesser hazard group when evaluated in accordance with Table No. VI-2.

     (3) When a change of occupancy is made to a higher hazard group as shown in Table No. VI-3, occupancy separations shall be provided as specified in the Building Code. When approved by the building official, existing wood lath and plaster in good condition or one-half inch gypsum wall board may be accepted where a one hour occupancy separation is required.

     (4)(a) Vertical shafts may be designed to meet the requirements of atriums as required by the Building Code or the requirements of this chapter.

     (b) Interior stairways shall be enclosed as required by the Building Code when a change of occupancy is made to a higher hazard group as shown in Table No. VI-4.


EXCEPTIONS: (i) In other than Group I Occupancies, an enclosure will not be required for openings serving only one adjacent floor and not connected with corridors or stairways serving other floors.
(ii) Existing stairways not enclosed need not be enclosed in a continuous vertical shaft if each story is separated from other stories by one hour fire resistive construction or approved wired glass set in steel frames and all exit corridors are sprinklered. The openings between the corridor and occupant space shall have at least one quick response sprinkler head above the openings on the tenant side, with a draft gasket assembly on sound, solid, self-closing doors. The sprinkler system may be supplied from the domestic water supply system, provided the system is of adequate pressure, capacity, and sizing for the combined domestic and sprinkler requirements.

     (c) Interior shafts, including, but not limited to, elevator hoistways, service and utility shafts, shall be enclosed with a minimum of one-hour fire-resistive construction.


EXCEPTIONS: (i) Vertical openings, other than stairways, need not be enclosed if the entire building is provided with an approved automatic sprinkler system. The sprinkler system may be supplied from the domestic water supply system, provided the system is of adequate pressure, capacity, and sizing for the combined domestic and sprinkler requirements.
(ii) Where one-hour fire-resistive floor construction is required, vertical shafts need not be enclosed when such shafts are blocked at every floor level by the installation of not less than two full inches of solid wood or equivalent construction.

     (d) All openings into such shafts shall be protected by fire assemblies having a fire protection rating of not less than one hour and shall be maintained self-closing or shall be automatic closing by actuation of a smoke detector. All other openings shall be fire protected in an approved manner. Existing fusible link-type automatic door-closing devices may be permitted if the fusible link rating does not exceed one hundred thirty-five degrees.



[Statutory Authority: RCW 19.27.120 and 19.27.074. 91-01-103, § 51-19-620, filed 12/18/90, effective 7/1/91.]