1) Soil-gas retarder membrane as specified in section 503.2.4;
|
|
2) Sealing of penetrations and joints as specified in section 503.2.5;
|
|
3) A three-inch continuous sealed radon pipe shall run from a point within the aggregate under each concrete slab to a
point outside the building;
|
|
4) Joints and connections shall be gas tight, and may be of either PVC schedule 40 or ABS schedule of equivalent in
wall thickness;
|
|
5) A label of "radon vent" shall be placed on the pipe so as to remain visible to the occupant;
|
|
6) Fan circuit and wiring as specified in section 503.2.7 and a fan.
|
If the sub-slab depressurization system is exhausted
through the concrete foundation wall or rim joist, the exhaust
terminus shall be a minimum of six feet from operable windows
or outdoor air intake vents and shall be directed away from
operable windows and outdoor air intake vents to prevent radon
re-entrainment.