| EXCEPTION: | Where occupancy density is known and documented in the plans, the outside air rate may be based on the design occupant density. Under no circumstance shall the occupancies used result in outside air less than one-half that resulting from application of Table 3-4 estimated maximum occupancy values. |
| EXCEPTION: | Ducts may terminate within 12 inches of the intake to an HVAC unit provided they are physically fastened so that the outside air duct is directed into the unit intake. |
| Bathrooms | Kitchens | |
| Intermittently operating | 50 cfm | 100 cfm |
| Continuous operation | 20 cfm | 25 cfm |
| Floor Area, ft2 |
Bedrooms | |||||||||||||
| 2 or less | 3 | 4 | 5 | 6 | 7 | 8 | ||||||||
| Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | Min. | Max. | |
| <500 | 50 | 75 | 65 | 98 | 80 | 120 | 95 | 143 | 110 | 165 | 125 | 188 | 140 | 210 |
| 501-1000 | 55 | 83 | 70 | 105 | 85 | 128 | 100 | 150 | 115 | 173 | 130 | 195 | 145 | 218 |
| 1001-1500 | 60 | 90 | 75 | 113 | 90 | 135 | 105 | 158 | 120 | 180 | 135 | 203 | 150 | 225 |
| 1501-2000 | 65 | 98 | 80 | 120 | 95 | 143 | 110 | 165 | 125 | 188 | 140 | 210 | 155 | 233 |
| 2001-2500 | 70 | 105 | 85 | 128 | 100 | 150 | 115 | 173 | 130 | 195 | 145 | 218 | 160 | 240 |
| 2501-3000 | 75 | 113 | 90 | 135 | 105 | 158 | 120 | 180 | 135 | 203 | 150 | 225 | 165 | 248 |
| 3001-3500 | 80 | 120 | 95 | 143 | 110 | 165 | 125 | 188 | 140 | 210 | 155 | 233 | 170 | 255 |
| 3501-4000 | 85 | 128 | 100 | 150 | 115 | 173 | 130 | 195 | 145 | 218 | 160 | 240 | 175 | 263 |
| 4001-5000 | 95 | 143 | 110 | 165 | 125 | 188 | 140 | 210 | 155 | 233 | 170 | 255 | 185 | 278 |
| 5001-6000 | 105 | 158 | 120 | 180 | 135 | 203 | 150 | 225 | 165 | 248 | 180 | 270 | 195 | 293 |
| 6001-7000 | 115 | 173 | 130 | 195 | 145 | 218 | 160 | 240 | 175 | 263 | 190 | 285 | 205 | 308 |
| 7001-8000 | 125 | 188 | 140 | 210 | 155 | 233 | 170 | 255 | 185 | 278 | 200 | 300 | 215 | 323 |
| 8001-9000 | 135 | 203 | 150 | 225 | 165 | 248 | 180 | 270 | 195 | 293 | 210 | 315 | 225 | 338 |
| >9000 | 145 | 218 | 160 | 240 | 175 | 263 | 190 | 285 | 205 | 308 | 220 | 330 | 235 | 353 |
| *For residences that exceed 8 bedrooms, increase the minimum requirement listed for 8 bedrooms by an additional 15 CFM per bedroom. The maximum CFM is equal to 1.5 times the minimum. | ||||||||||||||
| Fan
Tested CFM @ 0.25 W.G. |
Minimum Flex Diameter |
Maximum Length Feet |
Minimum Smooth Diameter |
Maximum Length Feet |
Maximum Elbows1 |
| 50 | 4 inch | 25 | 4 inch | 70 | 3 |
| 50 | 5 inch | 90 | 5 inch | 100 | 3 |
| 50 | 6 inch | No Limit | 6 inch | No Limit | 3 |
| 80 | 4 inch2 | NA | 4 inch | 20 | 3 |
| 80 | 5 inch | 15 | 5 inch | 100 | 3 |
| 80 | 6 inch | 90 | 6 inch | No Limit | 3 |
| 100 | 5 inch2 | NA | 5 inch | 50 | 3 |
| 100 | 6 inch | 45 | 6 inch | No Limit | 3 |
| 125 | 6 inch | 15 | 6 inch | No Limit | 3 |
| 125 | 7 inch | 70 | 7 inch | No Limit | 3 |
| 1. | For each additional elbow subtract 10 feet from length. |
| 2. | Flex ducts of this diameter are not permitted with fans of this size. |
| Application | Estimated Maximum2 Occupancy P/1000 ft2 or 100 m2 |
Outdoor Air Requirements cfm/person |
| Dry Cleaners, Laundries3 | ||
| Commercial laundry | 10 | 25 |
| Commercial dry cleaner | 30 | 30 |
| Storage, pick up | 30 | 35 |
| Coin-operated laundries | 20 | 15 |
| Coin-operated dry cleaner | 20 | 15 |
| Dwelling Units In Buildings Greater Than Four Stories or Attached to
I- Occupancy Facilities |
||
| Bedroom & living area24 | 15 | |
| Food and Beverage Service | ||
| Dining rooms | 70 | 20 |
| Cafeteria, fast food | 100 | 20 |
| Bars, cocktail lounges4 | 100 | 30 |
| Kitchens (cooking)23 | 20 | 15 |
| Garages, Repair, Service Stations | ||
| Enclosed parking garage5 | 1.50 cfm/ft.sq. | |
| Auto repair rooms | 1.50 cfm/ft.sq. | |
| Hotels, Motels, Resorts, Congregate Residences with More Than
Four Stories6 |
||
| Bedrooms | 30 cfm/room | |
| Living Rooms | 30 cfm/room | |
| Bath7 | 35 cfm/room | |
| Lobbies | 30 | 15 |
| Conference rooms | 50 | 20 |
| Assembly rooms | 120 | 15 |
| Gambling casinos4 | 120 | 30 |
| Offices | ||
| Office space9 | 7 | 20 |
| Reception area | 60 | 15 |
| Telecommunication centers and data entry areas |
60 | 20 |
| Conference rooms | 50 | 20 |
| Public Spaces | ||
| Corridors and utilities | 0.05 cfm/ft.sq. | |
| Public restroom, cfm/wc or urinal10 |
50 | |
| Lockers and dressing rooms | 0.50 cfm/ft.sq. | |
| Smoking lounge11 | 70 | 60 |
| Elevators12 | 1.0 cfm/ft.sq. | |
| Retail Stores, Sales Floors, and Show Room Floors | ||
| Basement and street | 30 | 0.30 cfm/ft.sq. |
| Upper floors | 20 | 0.20 cfm/ft.sq. |
| Storage rooms | 15 | 0.15 cfm/ft.sq. |
| Dressing rooms | 0.20 cfm/ft.sq. | |
| Malls and arcades | 20 | 0.20 cfm/ft.sq. |
| Shipping and receiving | 10 | 0.15 cfm/ft.sq. |
| Smoking lounge11 | 70 | 60 |
| Warehouses | 5 | 0.05 cfm/ft.sq. |
| Speciality Shops | ||
| Barber | 25 | 15 |
| Beauty | 25 | 25 |
| Reducing salons | 20 | 15 |
| Florists13 | 8 | 15 |
| Clothiers, furniture | 0.30 cfm/ft.sq. | |
| Hardware, drugs, fabric | 8 | 15 |
| Supermarkets | 8 | 15 |
| Pet shops | 1.00 cfm/ft.sq. | |
| Sports and Amusement14 | ||
| Spectator areas | 150 | 15 |
| Game rooms | 70 | 25 |
| Ice arenas (playing areas) | 0.50 cfm/ft.sq. | |
| Swimming Pools (pool and deck area)15 |
0.50 cfm/ft.sq. | |
| Playing floor (gymnasium) | 30 | 20 |
| Ballrooms and discos | 100 | 25 |
| Bowling alleys (seating areas) | 70 | 25 |
| Theaters16 | ||
| Ticket booths | 60 | 20 |
| Lobbies | 150 | 20 |
| Auditorium | 150 | 20 |
| Stages, studios | 70 | 15 |
| Transportation17 | ||
| Waiting rooms | 100 | 15 |
| Platforms | 100 | 15 |
| Vehicles | 150 | 15 |
| Workrooms | ||
| Meat processing18 | 10 | 15 |
| Photo studios | 10 | 15 |
| Darkrooms | 10 | 0.50 cfm/ft.sq. |
| Pharmacy | 20 | 15 |
| Bank vaults | 5 | 15 |
| Duplicating, printing19 | 0.50 cfm/ft.sq. | |
| INSTITUTIONAL FACILITIES | ||
| Education | ||
| Classroom | 50 | 15 |
| Laboratories20 | 30 | 20 |
| Training shop | 30 | 20 |
| Music rooms | 50 | 15 |
| Libraries | 20 | 15 |
| Locker rooms | 0.50 cfm/ft.sq. | |
| Corridors | 0.10 cfm/ft.sq. | |
| Auditoriums | 150 | 15 |
| Smoking lounges11 | 70 | 60 |
| Hospitals, Nursing and Convalescent Homes | ||
| Patient rooms21 | 10 | 25 |
| Medical procedure | 20 | 15 |
| Operating rooms | 20 | 30 |
| Recovery and ICU | 20 | 15 |
| Autopsy rooms22 | 0.50 cfm/ft.sq. | |
| Physical Therapy | 20 | 15 |
| Correctional Facilities | ||
| Cells | 20 | 20 |
| Dining halls | 100 | 15 |
| Guard station | 40 | 15 |
| 1. | Derived from ASHRAE Standard 62-1989. |
| 2. | Net occupiable space. |
| 3. | Dry-cleaning process may require more air. |
| 4. | Supplementary smoke-removal equipment may be required. |
| 5. | Distribution among people must consider worker location and concentration of running engine; stands where engines are run must incorporate systems for positive engine exhaust withdrawal. Contaminant sensors may be used to control ventilation. |
| 6. | Independent of room size. |
| 7. | Installed capacity for intermittent use. |
| 8. | See also food and beverage service, merchandising, barber and beauty shops, garages. |
| 9. | Some office equipment may require local exhaust. |
| 10. | Mechanical exhaust with no recirculation is recommended. |
| 11. | Normally supplied by transfer air, local mechanical exhaust; with no recirculation recommended. |
| 12. | Normally supplied by transfer air. |
| 13. | Ventilation to optimize plant growth may dictate requirements. |
| 14. | When internal combustion engines are operated for maintenance of playing surfaces, increased ventilation rates may be required. |
| 15. | Higher values may be required for humidity control. |
| 16. | Special ventilation will be needed to eliminate special stage effects. |
| 17. | Ventilation within vehicles may require special considerations. |
| 18. | Spaces maintained at low temperatures (-10°F. to + 50°F.) are not covered by these requirements unless the occupancy is continuous. Ventilation from adjoining spaces is permissible. When the occupancy is intermittent, infiltration will normally exceed the ventilation requirements. |
| 19. | Installed equipment must incorporate positive exhaust and control of undesirable contaminants. |
| 20. | Special contamination control systems may be required for processes or functions including laboratory animal occupancy. |
| 21. | Special requirements or codes and pressure relationships may determine minimum ventilation rates and filter efficiency. Procedures generating contaminants may require higher rates. |
| 22. | Air shall not be recirculated into other spaces. |
| 23. | Makeup air for hood exhaust may require more ventilating air. |
| 24. | Occupant loading shall be based on the number of bedrooms as follows: first bedroom, two persons; each additional bedroom, one person. Where higher occupant loadings are known, they shall be used. |
| Required Flow (CFM) Per Table 3-2 |
Minimum Smooth Duct Diameter |
Minimum Flexible Duct Diameter |
Maximum Length1 |
Maximum Number of Elbows2 |
| 50-80 | 6" | 7" | 20' | 3 |
| 80-125 | 7" | 8" | 20' | 3 |
| 115-175 | 8" | 10" | 20' | 3 |
| 170-240 | 9" | 11" | 20' | 3 |
| 1. | For lengths over 20 feet increase duct diameter 1 inch. |
| 2. | For elbows numbering more than 3 increase duct diameter 1 inch. |
| Supply Fan Tested CFM At 0.4" WG | ||
| Specified volume from Table 3-2 |
Minimum Smooth Duct Diameter |
Minimum Flexible Duct Diameter |
| 50-90 CFM | 4 inch | 5 inch |
| 90-150 CFM | 5 inch | 6 inch |
| 150-250 CFM | 6 inch | 7 inch |
| 250-400 CFM | 7 inch | 8 inch |