WAC 51-11-1331
General. Buildings or structures whose
design heat loss rate (UAp) and solar heat gain coefficient
rate (SHGC*Ap) are less than or equal to the target heat loss
rate (UAt) and solar heat gain coefficient rate (SHGC*At) shall
be considered in compliance with this section. The stated
U-factor, F-factor or allowable area of any component
assembly, listed in Tables 13-1 or 13-2, such as roof/ceiling,
opaque wall, opaque door, glazing, floor over conditioned
space, slab on grade floor, radiant floor or opaque floor may
be increased and the U-factor or F-factor for other components
decreased, provided that the total heat gain or loss for the
entire building envelope does not exceed the total resulting
from compliance to the U-factors, F-factors or allowable areas
specified in this section.
EXCEPTION:
Compliance is also allowed to be shown using RS-32 for Climate Zone 1.