| EXCEPTIONS: | 1. Opaque smoke vents are not required to meet insulation requirements. |
| 2. For prescriptive compliance only. | |
| a. For glazing areas that are 30% and less of the gross wall area, the insulation of the perimeter edge of an above grade floor slab which penetrates the exterior wall may be reduced to R-5 provided the glazing U-factor is reduced by U-0.05 below that required in Tables 13-1 and 13-2. | |
| b. For glazing areas that exceed 30% of the gross wall area, the perimeter edge of an above grade floor slab which penetrates the exterior wall may be left uninsulated provided that the glazing U-factor is reduced by U-0.10 below that required in Tables 13-1 and 13-2. |