WAC 51-11-0540   Table 5-11.  



TABLE 5-11

INSULATION OF DUCTS




DUCT LOCATION




CLIMATE ZONE
GROUP R OCCUPANCY

HEATING OR

COOLING DUCTS

On roof or on

exterior of building

I

II

E a          nd W

D and W
Attic, garage,

crawl space,

in walls1, in

floor/ceiling1




I

II




E

E
Within the conditioned space or in heated basement
 



None

Required
In cement slab

or in ground
 

B

Note: Where ducts are used for both heating and cooling, the minimum insulation shall be as required for the most restrictive condition.


1 Insulation may be omitted on that portion of a duct which is located within a wall or floor-ceiling space where both sides of this space are      exposed to conditioned air and where this space is not ventilated or otherwise exposed to unconditioned air.
2 Vapor barriers shall be installed on conditioned air supply ducts in geographic areas where the average of the July, August, and September      mean dewpoint temperature exceeds 60°F.
INSULATION TYPES: Minimum densities and out-of-package thickness.


A. 0.5-inch 1.5 to 2 lb/cu. ft. duct liner, mineral or glass fiber blanket or equivalent to provide an installed total thermal resistance of at least      R-2.
B. 2-inch 0.60 lb/cu. ft. mineral or glass fiber blanket 1.5-inch 1.5 to 2 lb/cu. ft. duct liner, mineral or glass fiber blanket. 1.5-inch 3 to 7      lb/cu. ft. mineral or glass fiber board or equivalent to provide an installed total thermal resistance of at least R-5.
C. 3-inch 0.60 lb/cu. ft. mineral or glass fiber blanket 2-inch 1.5 to 2 lb/cu. ft. duct liner, mineral or glass fiber blanket. 2-inch 3 to 7 lb/cu. ft.      mineral or glass fiber board or equivalent to provide an installed total thermal resistance of at least R-7.
D. 4-inch 0.60 lb/cu. ft. mineral or glass fiber blanket 3-inch 1.5 to 2 lb/cu. ft. duct liner, mineral or glass fiber blanket. 3-inch 3 to 7 lb/cu. ft.      mineral or glass fiber board or equivalent to provide an installed total thermal resistance of at least R-10.
E. 3.5 inch 0.60 lb/cu. ft. mineral or glass fiber blanket, 2.5 inch 1.5 to 2 lb/cu. ft. duct liner, mineral or glass fiberboard or equivalent to      provide an installed total thermal resistance of at least R-8.
V. Vapor barrier, with perm rating not greater than 0.5 perm, all joints sealed.
W. Approved weatherproof barrier.




[Statutory Authority: RCW 19.27A.022, 19.27A.025, 19.27A.045, and chapters 19.27 and 34.05 RCW. 07-01-089, § 51-11-0540, filed 12/19/06, effective 7/1/07. Statutory Authority: RCW 19.27A.025. 93-21-052, § 51-11-0540, filed 10/18/93, effective 4/1/94. Statutory Authority: Chapter 19.27A RCW. 92-01-140, § 51-11-0540, filed 12/19/91, effective 7/1/92.]