| EXCEPTIONS: | The following limited exemptions from the sizing limit shall be allowed; however, in all cases heating and/or cooling
design load calculations shall be submitted. |
| 1. For equipment which provides both heating and cooling in one package unit, including heat pumps with electric
heating and cooling and gas-pack units with gas heating and electric cooling, compliance need only be demonstrated for
either the space heating or space cooling system size. |
|
| 2. Natural gas- or oil-fired space heating equipment whose total rated space heating output in any one dwelling unit is |
|
| a. 40,000 Btu/h or less is exempt from the sizing limit, |
|
| b. Larger than 40,000 Btu/h may exceed the one hundred fifty (150%) percent sizing limit but not exceed 250 percent
provided that the installed equipment has an annual fuel utilization efficiency (AFUE) of ninety (90%) percent or
greater. |
|
| 3. Stand-by equipment may be installed if controls and other devices are provided which allow redundant equipment to operate only when the primary equipment is not operating. |
| EXCEPTION: | Special uses requiring different relative humidities may be permitted when approved by the building official. |
| EXCEPTIONS: | Duct insulation (except where required to prevent condensation) is not required in any of the following cases: |
| 1. When the heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the building. |
|
| 2. Within the HVAC equipment. |
|
| 3. Exhaust air ducts. |
|
| 4. Supply or return air ducts installed in unvented crawl spaces with insulated walls, basements, or cellars in one- and two-family dwellings. |
| EXCEPTIONS: | 1. Ducts or building cavities used for air distribution that are located entirely within the conditioned space of the building are exempt from this section. |
| 2. UL 181A listed tapes used with listed rigid fibrous glass ducts may be used as the primary sealant, when installed in accordance with the listing. | |
| 3. UL 181B listed tapes used with listed flexible air ducts may be used as the primary sealant, when installed in accordance with the listing. | |
| 4. Where enclosed stud bays or joist cavities/spaces are used to transport air sealing may be accomplished using drywall, drywall tape plus joint compound. | |
| 5. Tapes installed in accordance with the manufacturer's installation instructions, providing detailed information specific to application on ducts, including approved duct materials and required duct surface cleaning. |
| EXCEPTION: | Piping installed within unitary HVAC equipment. |
| EXCEPTIONS: | The following limited exemptions from the sizing limit shall be allowed; however, in all cases heating and/or cooling
design load calculations shall be submitted. |
| 1. For equipment which provides both heating and cooling in one package unit, including heat pumps with electric
heating and cooling and gas-pack units with gas heating and electric cooling, compliance need only be demonstrated for
either the space heating or space cooling system size. |
|
| 2. Natural gas- or oil-fired space heating equipment whose total rated space heating output in any one dwelling unit is |
|
| a. 40,000 Btu/h or less is exempt from the sizing limit, |
|
| b. Larger than 40,000 Btu/h may exceed the one hundred fifty (150%) percent sizing limit but not exceed 250 percent
provided that the installed equipment has an annual fuel utilization efficiency (AFUE) of ninety (90%) percent or
greater. |
|
| 3. Stand-by equipment may be installed if controls and other devices are provided which allow redundant equipment to operate only when the primary equipment is not operating. |
| EXCEPTION: | Special uses requiring different relative humidities may be permitted when approved by the building official. |
| EXCEPTIONS: | Duct insulation (except where required to prevent condensation) is not required in any of the following cases: |
| 1. When the heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the building. |
|
| 2. Within the HVAC equipment. |
|
| 3. Exhaust air ducts. |
|
| 4. Supply or return air ducts installed in unvented crawl spaces with insulated walls, basements, or cellars in one- and two-family dwellings. |
| EXCEPTIONS: | 1. Duct tightness test is not required if the air handler and all ducts are located within conditioned space. |
| 2. Duct tightness test is not required if the furnace is a nondirect vent type combustion appliance installed in an unconditioned space. A maximum of six feet of connected ductwork in the unconditioned space is allowed. All additional supply and return ducts shall be within the conditioned space. Ducts outside the conditioned space shall be sealed with a mastic type duct sealant and insulated on the exterior with R-8 insulation for above grade ducts and R-5 water resistant insulation when within a slab or earth. |
| EXCEPTION: | Piping installed within unitary HVAC equipment. |