| EXCEPTIONS: | The following limited exemptions from the sizing limit shall be allowed; however, in all cases heating and/or cooling
design load calculations shall be submitted. |
| 1. For equipment which provides both heating and cooling in one package unit, including heat pumps with electric
heating and cooling and gas-pack units with gas heating and electric cooling, compliance need only be demonstrated for
either the space heating or space cooling system size. |
|
| 2. Natural gas- or oil-fired space heating equipment whose total rated space heating output in any one dwelling unit is |
|
| a. 40,000 Btu/h or less is exempt from the sizing limit, |
|
| b. Larger than 40,000 Btu/h may exceed the one hundred fifty (150%) percent sizing limit but not exceed 250 percent
provided that the installed equipment has an annual fuel utilization efficiency (AFUE) of ninety (90%) percent or
greater. |
|
| 3. Stand-by equipment may be installed if controls and other devices are provided which allow redundant equipment to operate only when the primary equipment is not operating. |
| EXCEPTION: | Special uses requiring different relative humidities may be permitted when approved by the building official. |
| EXCEPTIONS: | Duct insulation (except where required to prevent condensation) is not required in any of the following cases: |
| 1. When the heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the building. |
|
| 2. Within the HVAC equipment. |
|
| 3. Exhaust air ducts. |
|
| 4. Supply or return air ducts installed in unvented crawl spaces with insulated walls, basements, or cellars in one- and two-family dwellings. |
| EXCEPTIONS: | 1. Ducts or building cavities used for air distribution that are located entirely within the conditioned space of the building are exempt from this section. |
| 2. UL 181A listed tapes used with listed rigid fibrous glass ducts may be used as the primary sealant, when installed in accordance with the listing. | |
| 3. UL 181B listed tapes used with listed flexible air ducts may be used as the primary sealant, when installed in accordance with the listing. | |
| 4. Where enclosed stud bays or joist cavities/spaces are used to transport air sealing may be accomplished using drywall, drywall tape plus joint compound. | |
| 5. Tapes installed in accordance with the manufacturer's installation instructions, providing detailed information specific to application on ducts, including approved duct materials and required duct surface cleaning. |
| EXCEPTION: | Piping installed within unitary HVAC equipment. |