| EXCEPTIONS: | 1. Foam plastic insulation shall comply with section 2603 of the International Building Code. |
| 2. When such materials are installed in concealed spaces of Types III, IV and V construction, the flame spread and
smoke developed limitations do not apply to facing, provided that the facing is installed in substantial contact with the
unexposed surface of the ceiling, floor or wall finish. |
|
| 3. Cellulose insulation shall comply with section 719 of the International Building Code. |
| EXCEPTION: | Framed cavity can be empty or partially filled provided: |
| 1. The wall assembly calculations are performed along with a completed performance calculation for the whole building; and | |
| 2. Insulation installed in partially filled cavities is not included in the performance calculation. |
| EXCEPTION: | Insulation may be omitted from floor areas over heated basements, heated garages or underfloor areas used as HVAC supply plenums. When foundation walls are insulated, the insulation shall be attached in a permanent manner. The insulation shall not block the airflow through foundation vents when installed. When foundation vents are not placed so that the top of the vent is below the lower surface of the floor insulation, a permanently attached baffle shall be installed at an angle of 30° from horizontal, to divert air flow below the lower surface of the floor insulation. |
| EXCEPTION: | For monolithic slabs, the insulation shall extend downward from the top of the slab to the bottom of the footing. |
| EXCEPTIONS: | 1. For glazed wall systems, assemblies with all of the following features are deemed to satisfy the vertical glazing
U-factor requirement in Table 6-1 or 6-2 options with vertical glazing U-0.40 and greater: |
| a. Double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e = 0.10 maximum, with
90% minimum argon gas fill, and a non-aluminum spacer (as defined in footnote 1 to Table 10-6B), and |
|
| b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad wood, vinyl,
aluminum clad vinyl, or reinforced vinyl. |
|
| The only labeling requirement for products using this exception shall be a description of the product and a label stating:
"This product is deemed to satisfy the Table 6-1 or 6-2 vertical glazing U-factor requirement using the exception to
Section 502.1.5 in the Washington State Energy Code." |
|
| 2. For overhead glazing, assemblies with all of the following features are deemed to satisfy the overhead glazing
U-factor requirement in Table 6-1 or 6-2 options except the unlimited glazing area options (Options IV and V in
Table 6-1 and Options V, VI and VII in Table 6-2): |
|
| a. Either, double glazing with a minimum 1/2 inch gap width, having a low-emissivity coating with e = 0.20 maximum,
with 90% minimum argon gas fill, or, triple glazed plastic domes, and |
|
| b. Frame that is thermal break aluminum (as defined in footnote 9 to Table 10-6B), wood, aluminum clad wood, vinyl,
aluminum clad vinyl, or reinforced vinyl. |
|
| The only labeling requirement for products using this exception shall be a description of the product and a label stating:
"This product is deemed to satisfy the Table 6-1 or 6-2 overhead glazing U-factor requirement using the exception to
Section 502.1.5 in the Washington State Energy Code." |
|
| 3. For solariums with a floor area which does not exceed 300 square feet, assemblies which comply with the features
listed in exception 2 are deemed to satisfy the vertical glazing and overhead glazing U-factor requirement in Table 6-1
or 6-2 options with vertical glazing U-0.40 and greater. |
|
| The only labeling requirement for products using this exception shall be a description of the product and a label stating:
"This product is deemed to satisfy the Table 6-1 or 6-2 vertical glazing and overhead glazing U-factor requirements
using the exception to Section 502.1.5 in the Washington State Energy Code." |
| EXCEPTIONS: | 1. Glazing products without NFRC ratings may be assigned default U-factors from Table 10-6A for vertical glazing and
from Table 10-6E for overhead glazing. |
| 2. Units without NFRC ratings produced by a small business may be assigned default U-factors from Table 10-6A for
garden windows, from Table 10-6B for other vertical glazing, and from Table 10-6E for overhead glazing. |
| EXCEPTIONS: | 1. U-factors determined, certified and labeled in accordance with the National Fenestration Rating Council (NFRC)
Product Certification Program (PCP), as authorized by an independent certification and inspection agency licensed by
the NFRC. |
| 2. The default values for the opaque portions of doors shall be those listed in Table 10-6C, provided that the U-factor
listed for a door with a thermal break shall only be allowed if both the door and the frame have a thermal break. |
|
| 3. One unlabeled or untested exterior swinging door with the maximum area of 24 square feet may be installed for
ornamental, security or architectural purposes. Products using this exception shall not be included in the U-factor
calculation requirements, however glazing area shall be included in glazing area calculations. |
| EXCEPTION: | Vapor retarder installed with not more than 1/3 of the nominal R-value between it and the conditioned space. |
| EXCEPTION: | For climate zone 1, wood framed walls with a minimum of nominal R-5 continuous insulated sheathing installed outside of the framing and structural sheathing. For climate zone 2, wood framed walls with a minimum of nominal R-7.5 continuous insulated sheathing installed outside of the framing and structural sheathing. The interior cavity insulation for this exception shall be a maximum of nominal R-21. |
| EXCEPTION: | The ground cover may be omitted in crawl spaces if the crawl space has a concrete slab floor with a minimum thickness of 3-1/2 inches. |
| EXCEPTION: | Log and solid timber walls that have a minimum average thickness of 3.5" and with space heat type other than electric resistance, are exempt from wall target UA and proposed UA calculations. |
| EXCEPTION: | Electric resistance systems for which the total electric heat capacity in each individual dwelling unit does not exceed the greater of: 1) One thousand watts (1000 w) per dwelling unit, or; 2) One watt per square foot (1 w/ft2) of the gross floor area. |