| PARAMETER | VALUE | |
| Thermostat set point, heating Thermostat set point, cooling Thermostat night set back Thermostat night set back period |
65° F 78° F 65° F 0 hours |
|
| Internal gain | ||
| R-3 and R-4 units R-1 and R-2 units |
3000 Btu/hr 1500 Btu/hr |
|
| Domestic Hot Water Heater Setpoint |
120° F |
|
| Domestic Hot Water Consumption |
20 gallons/person/day. | |
| Minimum heat storage | Calculated using standard engineering practice for the actual building or as approved. | |
Site weather data |
Typical meteorological year (TMY) or ersatz TMY data for the closest appropriate TMY site or other sites as approved. |
|
| Heating and cooling equipment efficiency |
Equipment shall comply with Section 1411. | |
| EXCEPTIONS: | Chapters 5, and 6 of this Code establish criteria for different energy-consuming and enclosure elements of the building which, will eliminate the requirement for an annual systems energy analysis while meeting the intent of this Code. |
| A building designed in accordance with this chapter will be deemed as complying with this Code if the calculated annual energy consumption is not greater than a similar building (defined as a "standard design") whose enclosure elements and energy-consuming systems are designed in accordance with Chapter 5. | |
| For an alternate building design to be considered similar to a "standard design," it shall utilize the same energy source(s) for the same functions and have equal floor area and the same ratio of envelope area to floor area, environmental requirements, occupancy, climate data and usage operational schedule. |
| EXCEPTION: | Group R Occupancy shall comply with calculation procedures in Chapter 8, or an approved alternate. |